Our Services :-

 

we want to make sure that you gain the maximum possible benefit from its purchase.You may wish to contract  with Akshat for regularly scheduled visits for the purpose of inspecting and reporting your tower’s condition to make recommendations intended to prevent emergencies and to perform maintenance considered out site the norm.

 

Replacement parts : 

A complete stock of all parts and components is maintained. In cases of emergency, they can be shipped immediately by a  reliable source. We will also try to give you service and spare part in your existing old other make Cooling Towers. For that you have to give us Tower serial no. which on nameplate or Akshat bill no etc. for other make C.T you can give Detail Dimension drawing.

Periodic maintenance :

We have already attached our product maintenance Schedule and Trouble Shooting so that you can do Periodic maintenance accordingly.

Keeping our customers as the nucleus of our business, we are committed to delivering quality products and services. We will strive to win our customer’s utmost satisfaction and delight through competitive cost, prompt delivery and after sales services. We will ensure that our products and services meet our customer’s present and future needs.

 

Guarantee :

All Components are guaranteed against defective materials for a period of one (1) year. When return to AKSHAT with transportation prepaid, all parts found by factory inspection to be defective will be repaired or replaced without charge, FOB Pardi works. Gujarat – India.

No liability will be assumed for loss or damage resulting from the misuse of our products.

 
Troubleshooting :-
TROUBLE
CAUSES
CORRECTIVE ACTIONS
Lowering of cooling Capacity :
Motor stoppage
1.
Electric blackout
- Contact power company
2.
Fuse burnout
- Get proper fuse
3.
Insufficient switch capacity.
-

Change to proper switch

4.
Bad switch contact
- Adjust contact
 
Sudden lowering of motor  rpm
1.
Bad y-A starter contact
- Adjusted contact
2.
Too heavy load
- Lighten to proper load
3.
Lowering of voltage
-

Consult power company

     
Cannot rev up motor rpm
1.
Bad Y-A improperly  connected
- Correct connection according to nameplate
2.
Connection of rotary and fixed section
-
Second out to repair shop
3.
Rotary wiring single phase short circuit
-

Send out to repair shop

     
Fan Stoppage
1.
Bad bearing
-
Exchange bearing.
Top
Temperature rise
Motor temperature rise
1.
Too heavy load
-

Lighten load to proper level

2.
Lowering of voltage
- Consult power company
3.
High surrounding temp
-

Send out to repair shop

4.
    Contact between rotary and fixed section.
- Change bearing or supplement grease.

 

5.
    Either damage in bearing or lack of grease
   
   
Oil leakage, others
    In case of gear speed      reduce oil leakage (5400,5500 models only)
1.
Too much oil
-
Lower the oil face to proper level

 

2.
Loose bolt
-
    Tighten properly
 
Rise in water

Temperature

1.
Water  flow above specified flow
-
Regulate to correct flow rate.

 

2.
Air flow below specified flow
-

Adjust blade angle check and clean jali.

3.
    Load hiher then design
 

Adjust load to correct level

4.
    Fill checked or coated
  Clean/replace fills. Use proper
5.
    Fresh air ilntake not sufficient or area around tower not at specified.
 

water(makeup) quality improve ventilation and ensure exhaust air does not get recycled.

6.
    WBT high
 

Check design condition and ensure no recycling of exhaust air.

7. Water by passing fills           

Check sprinkler head and pipe leakages.

8.

Sprinkler jammed/ water not being sprinkled and distributed

 

Repair sprinkler and distribution system.

   

Temperature

1.

Filters chocked

-

Clean water filter.

 

2.

Sprinkler pipes chocked

-

Clean pipes and holes

3. Level of water low in sump  

Adjust float/inlet flow ensure proper make-up

4.

Pump small

 

Replace for correct flow volume

  Top

Air flow low

1.

Fan speed low

-

Check bearings/motor

 

2.

Fan blade angle incorrect

-

Correct blade angle to required setting.

3.

Inlet jali chocked

 

Clean air path

   

Noise & Vibration

1.

Fan mounting loose

-

Tighten mounting bolts and correct/replace if needed.

2.

Fan blocks loose

-

Tighten blade in hub

3.

Fan unbalanced

 

Rebalance and adjust

4.

Motor bearing faulty

 

Check and grease or replace bearing on motor.

5.

Hub mounting on motor shaft loose

  Tighten and use end plate and Shims if required.
6.

Many parts rubing against Tower components

  Give proper clearances and adjust/align components.
   

Water carry over

1.
Sprinkler rotation too fast
-
Adjust sprinker angle as to match the specified rotation
2.

Blocking of filler

-

Clean up any blockage part

3.

Defective eliminator

 

Renew eliminator

4.

Sprinkler too high above filler

 

Adjust as specified.
       25mm ACT-8 to ACT-30
       50mm ACT-40 to ACT-8-
       75mm ACT-100 and up

  Top